    Re: Cold water pipe ground

    I'm near Chicago and my water meter has a jumper installed. However, the cold water pipe is my only ground. It's a 50-year old house.

    Is there a way to ground the electrical service from outside...
  2. Replies
    17
    Views
    54,445

    Re: Cold water pipe ground

    Thank you. That simplifies the process considerably.
  3. Replies
    17
    Views
    54,445

    Re: Cold water pipe ground

    I thought if you turn off the main breaker and disconnect the ground, you still have an ungrounded service panel with power inside it. Is this a safe option?
  4. Replies
    17
    Views
    54,445

    Re: Cold water pipe ground

    Yes, the main breaker is 100 amps. Doesn't length of the wire play a factor in determining the proper gauge? Tks.
  5. Replies
    17
    Views
    54,445

    Re: Cold water pipe ground

    Thank you. Do I connect the ground rod to the point on the service panel where it's presently connected to the cold water pipe? Do I run the ground cable to the ground rod in conduit (it has to go...
  6. Replies
    17
    Views
    54,445

    Re: Cold water pipe ground

    The electrical panel is grounded to the cold water pipe only. I see no ground rod connection outside at the meter. Tks.
  7. Replies
    17
    Views
    54,445

    Cold water pipe ground

    My 50 year old house uses a cold water pipe for the electrical ground. I need to replace that cold water pipe and am concerned about removing the ground while the plumbing work is being done. What do...